Technical Guide
2026-11-12 · Engineering
Film fill is the cheapest part of a cooling tower and the first thing winter takes out. It does not need a catastrophic freeze: one night at −6 °C with the fans running and flow cut back for turndown is enough to bridge the air gaps at the fill face, crack 0.35 mm sheet along the flute folds, and load beams sized for wet pack and nothing more. Most of the damage stays invisible until spring, when the tower derates and the fill comes out in pieces.
Three mechanisms cause almost all winter fill damage, and each needs a different fix.
Ice weighs about 917 kg/m³, so 1 mm over 1 m² is 0.92 kg. A 20 mm rime layer on a 10 × 10 m fill face is 1.8 tonnes, sitting where the pack is already heaviest. Support design in most towers assumes 60–80 kg/m² for 1.2 m of wet fill — the 73 kg/m² (15 psf) figure in most specifications — at 1/300 deflection.
| Component | Normal load | 20 mm ice | Failure mode |
|---|---|---|---|
| Fill, 1.2 m deep, wet | 60–80 kg/m² | +18 kg/m² | Sheet buckling, sag past 1/300 |
| Air inlet louver | 8–12 kg/m² | +18–25 kg/m² | Blade bow, splash-out, ice shedding |
| Drift eliminator | 4–6 kg/m² | +10–15 kg/m² | Blade sag, drift rate climbs |
| Fan deck beams | Icicles | 20–60 kg/m | Anchor cracking, ice falls onto fill |
That ice does not have to break a beam to cost money. It bridges the 6–8 mm gaps between sheets, air-side pressure drop rises 20–40%, and the fan pays the difference while approach drifts up 1–2 °C.
Freezing is a flow problem before it is a fill problem.
Four specification changes matter. Use 0.45 mm sheet rather than 0.35 mm: the heavier gauge survives a freeze-thaw cycle that cracks thin film along the fold. Take 20 mm flute spacing over 16 mm where duty allows, because the wider gap sheds ice instead of bridging it. Specify glue-free blocks so a damaged module swaps without dismantling the bay — CF series cross-fluted fill in 610 and 810 mm depths assembles flat in the bay with no adhesive cure. And pair counterflow fill with an M- or S-type air inlet louver to cut the recirculation that feeds ice on the louver face.
Keep PVC below 50–55 °C hot water; above that the sheet softens, and a frozen block will not spring back. On round towers, VF series vertical-flow counterflow fill is the direct replacement in the same 450 micron sheet. Expect USD 95–150 per m³; a frozen-out bay costs that again in rigging and lost capacity.
Inspection before the first frost, in order:
Winter damage is rarely one bad night. It is 50% flow, a 0.35 mm sheet and a recirculating louver, repeated for three months. Fix the flow rule and move to 0.45 mm sheet at 20 mm spacing, and the tower comes through the season with its approach intact.
Send tower type, cell dimensions, design flow and the coldest ambient the plant sees; we will return a winter-ready specification with block weights and load per beam.